| Type |
Contacted type Level Transmitter
|
|
| Certificate |
Ex d, KCS, CE, Rohs, IP66
|
|
| Feature |
PVC coating
|
|
| Range |
0.15 to 4 meter
|
|
| Technology |
Capacitance
|
|
| Applicable condition |
Max 20 bar in Tank up to 100 deg C Sticky, Corrosive, no Foam, Not able to calibrate at the application
|
|
| Point Feature | Sticky(High Viscosity)/ Liquid/ Solid application |

Level transmiter ALT6600 Autrol
| Model Name | ALT6600 | |
| Protocol | Digital Communication, HART | |
| Trim ability | Zero | |
| Power supply & Load Requirement | 250 to 550 ohm @ 24 Vdc, Loop Powered | |
| Falure Mode | Low ≤ 3.78 mA, High ≥ 21.1 mA | |
| External Buttons | Zero & Span 2 buttons for device configuration | |
| Process Temp. limit | -40 to 80℃ ( -104 to 176℉ ) | |
| Accuracy | ± 0.5% of Full Scale |